DK 3000
| SPECIFICATIONS |
| Nominal Power |
3000 VA |
| Active Power |
2100 W |
| Technology |
On Line Double Conversion VFI |
| INPUT |
| Input Voltage |
230 V |
| Input Voltage Range |
160V÷288V |
| Input Power Factor |
> 0,99 full load |
| Input Frequency |
50Hz / 60 Hz +/- 5% Autosensing |
| OUTPUT |
| Output Voltage |
230 V +/- 1% |
| Output Frequency |
50 Hz / 60 Hz ± 1Hz |
| Wave form |
Sinusoidal |
| Crest Factor |
3:1 |
| BATTERIES |
| Runtime @ 50% load |
16' |
| Runtime @ 80% load |
8' |
| Runtime Extendibility |
Yes |
| GENERAL SPECIFICATIONS |
| Signals and Alarms |
Led and acoustic signals
|
| Communication Ports |
Standard RS 232 & USB Interfaces plus communication Slot for SNMP Adapters, Dry Contact, Relay Boards, etc etc |
| Software |
Download free of charge from the website (www.metasystem.it) |
| Protection |
Electronic protection against overloads and short circuits. Operation blocked at the end of runtime or overheating Automatic shutdown for protections triggering
|
| Output Sockets |
4 IEC 320 |
| MECHANICAL SPECIFICATION |
| Net Weight |
30 kg |
| Dimensions (W x H x D) |
440 x 88 (2U) x 650 mm |
| ENVIRONMENTAL DATA |
| Working Temperature |
0 °C ÷ 40 °C |
| Relative Humidity |
0 % ÷ 90 % non condensing |
| Acoustic Noise @ 1 mt |
< 50 dBA |
| STANDARS |
| Standards |
EN 62040-1-1, EN 62040-2, EN 62040-3
|
| GUARANTEE |
| Guarantee |
2 years, including batteries |
|